  • Refrigerant Seminar
Download London map Download Refrigerant Seminar Presentation
(???Mb Powerpoint file)
 
  • T.E.W.I.

Below we show a TEWI (Total Equivalent Warming Impact) comparison. TEWI is a statistic which is being quoted on a more regular basis these days and we thought this information may be of interest.


TEWI = (GWP x L x n) + (GWP x m [1-a] + (n x E x b )
          leakage losses +  recovery losses  +  energy consumption
         ( direct global warming potential)  + (indirect global warming potential)

GWP   =  global warming potential [equivalent CO2 -related ]
L          =  leakage rate per year [Kg] (typical 10% of charge/ year)
n          =   system operating time [ years ]
m         =   refrigerant charge [Kg]
a          =   recycling factor (charge lost during end of life recovery)
E         =   energy consumption per year [ Kwh]
b          =   CO2 – emissions Kg per Kwh (energy- mix)

(European/UK  average CO2 equivalent   =   0.6/0.43)




TEWI comparison

NH3 vs. R407c  Water cooled water chillers 1,000Kw
TEWI NH3 = (0x{160x10%}x15)+(0x160x{1-0.75})+(15x{1,040X222}x 0.6)
                          (0 )                         (0)                 ( 2,077,920) = 2,077,920 KgCO2e

TEWI R407c= (1725x{160x10%}x15)+(1725x160x{1-0.75})+(15x{1,040X250}x 0.6)
                          (414,000 )                  (69,000)          ( 2,340,000)  = 2,823,000 KgCO2e
 
Compared to Ammonia R407C;
( leakage effects +100%)      (recovery loss +100%)       (energy effects +12.6%)

Overall effect + 36%



Assumptions:

  • 15 year life
  • Multi screw compressors machines
  • DX evaporators
  • 2,500 equivalent operating full load hours per annum
  • CHW 6 – condenser water 30<35 deg C
  • Refrigerant charge
  • Energy consumption
  • COP NH3/407c = 4.5 /4.0
  • CO2 emissions Kg per Kw/Hr (0.6 typical for Europe)
 